On May 22, the UNE 171.330 standard was published, focusing on the Indoor Air Quality (IAQ) Review, describing a methodology for carrying out an indoor environmental quality control plan. Unlike its predecessors, UNE 171.330-1:2008 and UNE 171.330-2:2014, which aimed at Diagnosis and Inspection, respectively.
The scope of application remains unchanged, excluding industrial and agricultural activities. It also refers to the application of UNE 171.340 for Controlled Environment Zones in Hospitals and UNE 171.350 for Hospitality Establishments.
To correctly apply the standard, it is essential to understand the classification of HVAC equipment in HVAC (Heating, Ventilation, and Air Conditioning) installations:
Type A HVAC Equipment
Air treatment units for large surfaces, powered by centralized systems. Known as AHUs (Air Handling Units), they generally include most stages described for such equipment. They are usually associated with All-Air units or fresh air supply units in mixed Air-Water systems.
Type B HVAC Equipment
Air treatment units with thermal capacities between 5 and 20 kW (in cooling or heating). They are typically intended for medium-sized areas and usually correspond to compact systems that include cooling and heating production elements within the same unit (Rooftop units, autonomous units, etc.).
Type C HVAC Equipment
Air treatment units with thermal capacities below 5 kW (in cooling or heating). They are typically small units used for fine temperature adjustment in specific areas of a given zone. They include fan coil units, VRF units, indoor heat pump units (split type), window units, etc.
Type D HVAC Equipment
Ventilation units without heat exchange batteries, such as energy recovery units.
The IAQ control plan for a building consists of the following phases:
As indicated by the standard, the flowchart to be followed is as follows:
Brief description of each step in the flowchart:
Some of the most important aspects that affect IAQ are as follows:
This involves determining whether the risk associated with these aspects should be evaluated (Quantifying the potential negative effect on IAQ through analysis, direct measurements, and/or visual inspections).
The risk matrix (probability/effects) used is as follows:
Effects are classified as follows:
With the significant environmental aspects evaluated, an assessment must be conducted using tests, direct measurements, visual inspections, and/or document reviews. These actions will determine if the potentially negative situations are actually affecting IAQ.
It is mandatory to perform at least one measurement of all mandatory minimum parameters outdoors.
The mandatory minimum parameters to be analyzed are, at least annually:
A minimum number of sampling points in the building for mandatory parameters is established.
Optionally, at the discretion of the TSCAI, the following can also be evaluated:
Fungi and bacteria in the ducts, formaldehyde, ambient lighting, noise, electromagnetic fields, static electricity, nitrogen oxides, fiberglass, ozone, thermal comfort analysis (UNE EN ISO 7730), sulfur dioxide, radon gas, allergens and sensitizers, endotoxins, and mycotoxins.
For each type of system (A, B, C, or D), the following tests must be conducted:
HVAC EQUIPMENT (TYPES A, B, C, AND D)
SUPPLY AIR DUCT. SUPPLY AND EXHAUST AIR DUCT
At least 25% of AHUs must be inspected, with equipment rotation to cover all units within 4 years.
Systems B, C, and D will be inspected according to the law.
Indoor environmental quality is based on two criteria:
Acceptable Value: A value intended to preserve the well-being and health of occupants, depending on IDA.
Maximum Limit Value: Represents a concentration or absolute value that must never be exceeded. If exceeded, even once and for a single parameter, it would result in a complete non-conformity of the building or installation.
These values are listed in Table 7 of the UNE standard. Below, we present the reference values for Total Volatile Organic Compounds (TVOCs).
(3) If the Acceptable Value is exceeded at any point, it is recommended to identify TVOCs by collection on an absorbent tube and laboratory analysis (Annex C).
A building is considered conforming if it meets the following requirements:
More articles
Interested in other (technical) knowledge articles? Keep yourself up to date and read them all